PERFORMANCE ASSESSMENT OF SUBSTATION SITE EARTHING USING FLUKE 1625 GROUND TESTER
DOI:
https://doi.org/10.4314/njt.321.607Keywords:
Substation, ground tester, earth impedance, protection.Abstract
This study utilizes the automatic frequency control (AFC) feature in Fluke 1625 ground tester to analyze earth impedance in five power substations. Other conventional methods like the use of megger for impedance test runs short of responding to variation in supply frequency and not trustworthy. Earthing is the fundamental requirement for protection in all electrical installations. The result shows that the use of the Fluke 1625 for ground testing is very reliable, hence the need for the performance assessment of this instrument as compare to the conventional system.
Downloads
Issue
Section
License
The contents of the articles are the sole opinion of the author(s) and not of NIJOTECH.
NIJOTECH allows open access for distribution of the published articles in any media so long as whole (not part) of articles are distributed.
A copyright and statement of originality documents will need to be filled out clearly and signed prior to publication of an accepted article. The Copyright form can be downloaded from http://nijotech.com/downloads/COPYRIGHT%20FORM.pdf while the Statement of Originality is in http://nijotech.com/downloads/Statement%20of%20Originality.pdf
For articles that were developed from funded research, a clear acknowledgement of such support should be mentioned in the article with relevant references. Authors are expected to provide complete information on the sponsorship and intellectual property rights of the article together with all exceptions.
It is forbidden to publish the same research report in more than one journal.